Skip to content

EPC / EPR

pH & ORP Controller · 9 models

EPC

Overview

Industrial pH/ORP controllers and recorders with high input impedance IC for high reliability and safety. Simultaneous display of measurement and set values. Simple operation for better ease of use.

Features

  • One-touch calibration — insert electrode into standard solution and press CAL.
  • Flexible power source — supports AC 90 to 260 V.
  • Functions as both pH and ORP meter via panel switch.
  • Memory backup — settings and calibration values preserved when powered off.
  • Wide transmission output range — 8 ranges for pH and 8 ranges for ORP.
  • Automatic electrode diagnostics — asymmetry potential, sensitivity, reaction speed.

Models

EPC-96AC EPC-96ACT EPC-100AC EPC-1 EPC-2 EOC-2 EPR-1S EPR-420S EPR-6S

Specifications

Measurement Range

EPC-96AC pH 0–14 · ORP 1400 mV
EPC-96ACT pH 0–14 · ORP 1400 mV
EPC-100AC pH 0–14 · ORP 2000 mV

Reproducibility

All EPC models pH ±0.05 · ORP ±5 mV

Transmission Output

All EPC models DC 4–20 mA (insulated I/O)
Max. load 500 Ω
Linearity ±0.5%

Control Contact Output

Channels 2-CH independent (IC contact)
Capacity AC 250 V, 3 A max (resistive)

Ambient Temperature & Humidity

EPC-96AC / 96ACT −5 to 40 °C · 85% RH or less
EPC-100AC −5 to 50 °C · 85% RH or less

Power Supply

EPC-96AC / 96ACT AC 90–260 V · 50/60 Hz · 10 W
EPC-100AC AC 100–115 V or 200–240 V · 50/60 Hz · 7 VA

Dimensions

EPC-96AC / 96ACT 96 × 96 × 145 mm (panel mount)
EPC-100AC 270 × 186 × 229 mm (rain-proof)

Weight

EPC-96AC / 96ACT Approx. 650 g
EPC-100AC Approx. 3 kg

Applications

  • Industrial pH and ORP measurement and control.
  • Plating plants, chemical plants, effluent treatment.
  • Food processing plants, laboratories, hospitals.
  • Rain-proof outdoor installations (EPC-100AC).
← Back to Accessories